This really has nothing to do with the question since the question is about the dimmer load, not the circuit load. You can only load the breaker to 80% as you said which is 12amps but the question is about a dimmer switch which can only be loaded to 150w or 1.25A at 120v. OP cannot put 182 LED lights on his dimmer switch.